Skip to content
New issue

Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.

By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.

Already on GitHub? Sign in to your account

FB to support IE514 GHC connected to IM40 controller #120

Open
wants to merge 1 commit into
base: master
Choose a base branch
from

Conversation

janezg-SLAC
Copy link
Contributor

@janezg-SLAC janezg-SLAC commented May 24, 2024

Description

Function block to support new high vacuum gauge IE514 for DREAM, connected to IM540 controller

Motivation and Context

How Has This Been Tested?

Tested in setup lab with one gauge.

Where Has This Been Documented?

Pre-merge checklist

  • Code works interactively
  • Code contains descriptive comments
  • Test suite passes locally
  • Libraries are set to Always Newest version (Library, *)
  • Committed with pre-commit or ran pre-commit run --all-files

@janezg-SLAC janezg-SLAC requested a review from jyin999 May 24, 2024 21:17
VAR CONSTANT
cMaxPressure : REAL := 7.5E-5; //Torr
cMinPressure : REAL := 7.5E-14; //Torr
cGaugeMinVoltage : REAL := 1.111; //minimum voltage corresponds to 7.5E-13 (7.498E-13)Torr which should be the minimum pressure IE514 can read.
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

If 7.5E-13 is the mininum pressure IE514 can read, why the cMinPressure is 7.5E-14? Are all readings < 1v false reading?