Schema Version 0.0.23
Primary Rule: False
Rule ID: 5-18
Rule Description: Manually controlled dynamic glazing shall use the average of the minimum and maximum SHGC and VT.
Appendix G Section: Section 5 Envelope
Appendix G Section Reference: Section G3.1-5(a)5 Building Envelope Modeling Requirements for the Proposed design
Applicability: All required data elements exist for P_RMR
Applicability Checks:
- The proposed building uses manually controlled dynamic glazing
Evaluation Context: Each Data Element
Data Lookup: None
Function Call: None
-
For each building segment in the Proposed model:
for building_segment_p in P_RMR.building.building_segments:
-
For each zone in building segment:
for zone_p in building_segment_p.zones:
-
For each surface in zone:
for surface_p in zone_p.surfaces:
- For each subsurface in surface:
for subsurface_p in surface_p.subsurfaces:
Rule Assertion:
- Case 1: If subsurface has manual dynamic glazing, outcome is UNDETERMINED:
if subsurface_p.dynamic_glazing_type == "MANUAL_DYNAMIC: outcome = UNDETERMINED and raise_message "SUBSURFACE ${subsurface_p} INCLUDES MANUALLY CONTROLLED DYNAMIC GLAZING IN THE PROPOSED DESIGN. VERIFY THAT SHGC AND VT WERE MODELED AS THE AVERAGE OF THE MINIMUM AND MAXIMUM SHGC AND VT."
- Case 2: Else, outcome is NOT_APPLICABLE:
else: outcome = NOT_APPLICABLE
- For each subsurface in surface:
-
-
Notes:
- Update Rule ID from 5-39 to 5-29 on 10/26/2023
- Update Rule ID from 5-29 to 5-18 on 12/22/2023