Rule ID: 15-5
Rule Description: Transformer efficiency reported in Baseline RMR equals Table 8.4.4
Rule Assertion: Baseline RMR = expected value
Appendix G Section: Transformers
Appendix G Section Reference: Table G3.1 15. Distribution Transformers
Data Lookup: Table 8.4.4
Evaluation Context: Each Data Element
Applicability Checks:
- Transformer is DRY_TYPE
- U_RMR transformer capacity is within range of Table 8.4.4
Manual Checks: None
- For each
_user_transformer
inU_RMR.transformers
:- Applicability Check 1:
_user_transformer.type == DRY_TYPE
- Get User transformer maximum regulated capacity:
if user_transformer.phase == SINGLE_PHASE: _user_max_capacity_limit = 333.0 else if _user_transformer.phase == THREE_PHASE: _user_max_capacity_limit = 1000.0
- Applicability Check 2:
_user_transformer.capacity >= 15.0 and _user_transformer.capacity <= _user_max_capacity_limit
- Get required User transformer efficiency:
_required_user_transformer_efficiency = data_lookup(table_8_4_4, _user_transformer.capacity, _user_transformer.phase)
- Applicability Check 3:
_user_transformer.efficiency >= _required_user_transformer_efficiency
- Find
_baseline_transformer
inB_RMR.transformers
with_baseline_transformer.name == _user_transformer.name
or report missing - Applicability Check 4:
_baseline_transformer.type == DRY_TYPE
- Get Baseline transformer maximum regulated capacity:
if _baseline_transformer.phase == SINGLE_PHASE: _baseline_max_capacity_limit = 333.0 else if _baseline_transformer.phase == THREE_PHASE: _baseline_max_capacity_limit = 1000.0
- Applicability Check 5:
_baseline_transformer.capacity >= 15.0 and _baseline_transformer.capacity <= _baseline_max_capacity_limit
- Get required Baseline transformer efficiency:
_required_baseline_transformer_efficiency = data_lookup(table_8_4_4, _baseline_transformer.capacity, _baseline_transformer.phase)
- Rule Assertion:
_baseline_transformer.efficiency == _required_baseline_transformer_efficiency