HVAC Device: Economizer
Vadim Tkachenko edited this page Oct 3, 2022
·
5 revisions
IMPORTANT: see Imperative vs. Reactive Code Base
The Wikipedia article on economizers is a good starting point.
Why Enthalpy Economizers Don't Work explains the role of humidity (though the title is a bit misleading).
An economizer is a device that will prevent the main HVAC device from switching on, and instead, turn itself on when conditions allow.
The economizer is connected to a zone.
- When the ambient temperature is more than
changeover delta
from the zone temperature, the economizer shuts off the HVAC and turns on. - When the zone temperature reaches the
target temperature
, the economizer turns off. - Zone setpoint plays no role in economizer operation.
- Setpoint 27°C, changeover delta 1°C, target temperature 22°C.
- Ambient 30°C, zone temperature 29°C: HVAC takes care of cooling.
- Ambient 28°C, zone temperature 29°C: economizer shuts off the HVAC and starts taking care of cooling.
- Ambient 22°C: economizer shuts off.