#!/usr/bin/env python3
# Copyright 2021 Arup
# MIT License
import minimalmodbus
import serial
#import os
import sys
PORT = '/dev/ttyUSB0'
BAUDRATE = 9600
def get_readings():
instrument = minimalmodbus.Instrument(PORT, 1)
instrument.serial.baudrate = BAUDRATE
instrument.serial.parity = serial.PARITY_NONE
instrument.serial.timeout = 0.5
instrument.serial.stopbits = 1
instrument.serial.bytesize = 8
instrument.serial.timeout = 0.5
print(instrument.read_string(29,20))
print(instrument.read_string(49,20))
print(instrument.read_string(69,20))
print("Current: ", instrument.read_float(2999))
print("Voltage: ", instrument.read_float(3027))
print("Active Power: ", instrument.read_float(3053), "kW")
print("Reactive Power: ", instrument.read_float(3067), "kVAR")
print("Apparent Power: ", instrument.read_float(3075), "kVA")
# need to process quadrant information in the datasheet
pf = instrument.read_float(3083)
if pf < 0:
if pf < -1:
print("Power factor: ", -2-pf, " leading")
else:
print("Power factor: ", pf, " lagging")
else:
if pf > 1:
print("Power factor: ", 2-pf, " leading")
else:
print("Power factor: ", pf, " lagging")
print("Cumulative active energy: ", instrument.read_float(45099), "Wh")
print("Cumulative reactive energy: ", instrument.read_float(45101), "VARh")
# starts here
try:
get_readings()
except:
# if we reach here we likely have had an I/O error on the serial port.
sys.stderr.write("System error: probably serial port IO.\n")
sys.exit(1)