Notifications
You must be signed in to change notification settings - Fork 0
/
Copy pathI_admissible.m
25 lines (22 loc) · 1.06 KB
/
I_admissible.m
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
function I_adm=I_admissible(Wd,T1,T2,T3,T4,n,R,Lambda1,Lambda2,Tmax,Tamb)
% This function finds the admissible current in accordance with
% IEC 60287-1-1, p11
I_adm=sqrt(((Tmax-Tamb)-Wd*(0.5*T1+n*(T2+T3+T4)))/(R*(T1+n*(1+Lambda1)*T2+n*(1+Lambda1+Lambda2)*(T3+T4))));
% Input:
% Wd - dielectric losses
% T1 - thermal resistance in RC scheme
% T2 - thermal resistance in RC scheme
% T3 - thermal resistance in RC scheme
% T4 - thermal resistance in RC scheme
% n - number of cores (3)
% R - electrical resistance
% Lambda1 - Ratio of the total losses in sheath respectively to the total
% conductor losses (or losses in one sheath to the losses in one
% conductor)(p24 IEC 60287-1-1)
% Lambda2, Ratio of the total losses in armour respectively to the total
% conductor losses (or losses in one sheath or armour to the losses
% in one conductor) p28 CEI 60287-1-1
% Tmax - maximal allowable temperature of cable, degC
% Tamb - ambient temperature, degC
% Output:
% I_adm - admissible current of cable, in A